Honeywell DR4300 User Manual

Page of 262
 
Input and Output Calibration for Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
155 
Step Description 
Press 
Action/Result 
Exit Calibration Mode 
FUNC
 
The recorder stores the span value. 
Repeat procedure for the other pen. Remove power from 
recorder and disconnect the milliammeter and connect 
output wiring. 
 
 
DISP
 
or 
SET 
 UP
 
To exit the calibration mode.