APC PDPM175G6H User Manual
150/175kw Modular PDU Installation
8
Bottom entry installation
Note: The sidecar is required for undefloor wiring into the PDU. The Sidecar does not contain a switch
or circuit breaker so a readily accessible disconnect device shall be incorporated external to the
equipment.
or circuit breaker so a readily accessible disconnect device shall be incorporated external to the
equipment.
1 Remove the dedicated cover plate. Drill holes
in the plate for conduits and re-install the
plate with the conduits installed. Route the
conductors (input conductors in single utility
systems or bypass conductors in dual utility
systems) through the bottom of the Side Car.
2 Connect the input/bypass conductors to the
L1, L2, L3, EGC, and GEC terminals and
torque to specifications on label.
Sidecar Model
PDU Model
PDPM150SC
PDPM150G6F
PDPM150L6F
PDPM150L6F
PDPM100SC
PDPM175G6H
pdx0878a