OPERATION
Eaton
®
 9130 UPS (700–3000 VA) User's Guide  
S
  164201718 Rev 2
 www.powerware.com
40
User Settings
The following table displays the options that can be changed by the user.
Table 3. User Settings  
Description
Available Settings
Default Setting
Change Language
[English] [French] [Spanish] [German]
[Russian]
Menus, status, notices, and alarms are in all
supported languages. UPS faults, Event Log
data, and settings are in English only.
English
User Password
[Enabled] [Disabled]
If Enabled is selected, the password is USER.
Disabled
Audible Alarms
[Enabled] [Disabled]
Enabled
Set Date and Time
NOTE  Time is a 24-hour clock.
Set Year, Month, Day, Hours, Minutes
Date: yyyy/mm/dd
Time: hh:mm
2008/01/01
12:00
Signal Inputs
Setup:  [Not Used] [Force Bypass]
[Remote Shutdown] [Delayed Shutdown]
[On Generator] [Building Alarm 1]
Active:  [High] [Low]
See “Programmable Signal Inputs” on
page 59.
RS232-3:  Not Used, High
cXSlot Serial:  Delayed
Shutdown, High
cXSlot Signal: Remote
Shutdown, Low
Relay Configuration
[UPS ok] [On Bypass] [On Battery]
[Battery Low] [Ext. Charger On]
See “Relay Output Contacts” on page 58.
Standard:  UPS ok
RS232-1:  Battery Low
RS232-8:  On Battery
cXSlot-K1:  On Battery
cXSlot-K2:  Battery Low
cXSlot-K3:  UPS ok
cXSlot-K4:  On Bypass
Serial Port Configuration
[1200 bps] [2400 bps] [9600 bps]
NOTE  USB communication requires 9600 bps.
RS232:  9600 bps
cXSlot:  9600 bps
Control Commands from Serial Port
[Enabled] [Disabled]
RS232:  Enabled
cXSlot:  Enabled
Output Voltage
[100V] [110V] [120V] [127V] [Autosensing]
[200V] [208V] [220V] [230V] [240V]
[Autosensing]
120V (low voltage models)
230V (high voltage models)
Output Frequency
[50Hz] [60Hz] [Autosensing]
Autosensing