OPERATION
Eaton
®
9130 UPS (700–3000 VA) User's Guide
S
164201718 Rev 2
www.powerware.com
41
Default Setting
Available Settings
Description
Frequency Converter
[Enabled] [Disabled]
If Enabled, the UPS operates as a frequency
converter, with bypass operation and all
bypass-related alarms disabled.
If Enabled, the UPS operates as a frequency
converter, with bypass operation and all
bypass-related alarms disabled.
Disabled
Overload Alarm Level
[10%] [20%] [30%] ... [100%]
These values affect alarm level only, not UPS
operation such as transfers or shutdown.
These values affect alarm level only, not UPS
operation such as transfers or shutdown.
100%
Generates the Output Overload
alarm at the set level.
Generates the Output Overload
alarm at the set level.
Transfer to Bypass When Overload*
[Immediate] [After Delay]
If Immediate, transfer occurs at load >102%.
If After Delay, transfer occurs according to
Table 19 on page 84.
If Immediate, transfer occurs at load >102%.
If After Delay, transfer occurs according to
Table 19 on page 84.
Immediate
Power Strategy
[Normal] [High Efficiency]
See “Setting Power Strategy” on page 48.
See “Setting Power Strategy” on page 48.
Normal
Automatic Start Delay
[Disabled] [No Delay] [1s] [2s]...[32767s]
If Disabled, automatic restart is not allowed.
See “Configuring Load Segments” on page 49.
If Disabled, automatic restart is not allowed.
See “Configuring Load Segments” on page 49.
Load Segment 1: No Delay
Load Segment 2: No Delay
Load Segment 2: No Delay
Automatic on Battery Shutdown
[Disabled] [No Delay] [1s] [2s]...[32767s]
Shutdown cancels if utility returns before the
delay expires. See “Configuring Load
Segments” on page 49.
Shutdown cancels if utility returns before the
delay expires. See “Configuring Load
Segments” on page 49.
Load Segment 1: Disabled
Load Segment 2: Disabled
Load Segment 2: Disabled
Start on Battery
NOTE Utility must be present and
output enabled at initial UPS startup.
output enabled at initial UPS startup.
[Enabled] [Disabled]
After initial startup, battery voltage must
exceed 2.10 volts per cell to start on battery.
After initial startup, battery voltage must
exceed 2.10 volts per cell to start on battery.
Enabled
Energy Saving Mode
[Disabled] [50W] [100W] ... [1000W]
UPS output is turned off if the UPS is on
battery and output power is below the
selected level.
UPS output is turned off if the UPS is on
battery and output power is below the
selected level.
Disabled
Remote Shutdown Delay
[No Delay] [1s] [2s]...[10800s]
No Delay
Delayed Shutdown Delay
[No Delay] [1s] [2s]...[10800s]
120s
Behavior on Rectifier Input Loss
NOTE Available only in >3000 VA
UPSs with separate supply sources
for the rectifier and bypass inputs.
UPSs with separate supply sources
for the rectifier and bypass inputs.
[Prefer Battery] [Prefer Bypass]
If Prefer Bypass, upon loss the UPS will
transfer to bypass in 3 seconds and remain as
long as bypass is available.
If Prefer Bypass, upon loss the UPS will
transfer to bypass in 3 seconds and remain as
long as bypass is available.
Prefer Battery
On Battery Notice Delay
[0] [1s] [2s]...[99s]
5s