Eaton Electrical 9130 User Manual

Page of 120
OPERATION
Eaton
®
 9130 UPS (700–3000 VA) User's Guide  
S
  164201718 Rev 2
 www.powerware.com
41
Default Setting
Available Settings
Description
Frequency Converter
[Enabled] [Disabled]
If Enabled, the UPS operates as a frequency
converter, with bypass operation and all
bypass-related alarms disabled.
Disabled
Overload Alarm Level
[10%] [20%] [30%] ... [100%]
These values affect alarm level only, not UPS
operation such as transfers or shutdown.
100%
Generates the Output Overload
alarm at the set level.
Transfer to Bypass When Overload*
[Immediate] [After Delay]
If Immediate, transfer occurs at load >102%.
If After Delay, transfer occurs according to
Table 19 on page 84.
Immediate
Power Strategy
Normal
Automatic Start Delay
[Disabled] [No Delay] [1s]  [2s]...[32767s]
If Disabled, automatic restart is not allowed.
See “Configuring Load Segments” on page 49.
Load Segment 1:  No Delay
Load Segment 2:  No Delay
Automatic on Battery Shutdown
[Disabled] [No Delay] [1s]  [2s]...[32767s]
Shutdown cancels if utility returns before the
delay expires. See “Configuring Load
Segments” on page 49.
Load Segment 1:  Disabled
Load Segment 2:  Disabled
Start on Battery
NOTE  Utility must be present and
output enabled at initial UPS startup.
[Enabled] [Disabled]
After initial startup, battery voltage must
exceed 2.10 volts per cell to start on battery.
Enabled
Energy Saving Mode
[Disabled] [50W] [100W] ... [1000W]
UPS output is turned off if the UPS is on
battery and output power is below the
selected level.
Disabled
Remote Shutdown Delay
[No Delay] [1s] [2s]...[10800s]
No Delay
Delayed Shutdown Delay
[No Delay] [1s] [2s]...[10800s]
120s
Behavior on Rectifier Input Loss
NOTE  Available only in >3000 VA
UPSs with separate supply sources
for the rectifier and bypass inputs.
[Prefer Battery] [Prefer Bypass]
If Prefer Bypass, upon loss the UPS will
transfer to bypass in 3 seconds and remain as
long as bypass is available.
Prefer Battery
On Battery Notice Delay
[0] [1s] [2s]...[99s]
5s