6  Troubleshooting
Issue A1
MICROMASTER 410    Operating Instructions
58
6SE6400-5EA00-0BP0
6.3 Fault 
messages
Fault
Possible Causes
Diagnose & Remedy
Reac-
tion
F0001
OverCurrent
Ø  Motor power (P0307) does not
correspond to the inverter power
(r0206)
Ø  Motor lead short circuit
Ø Earth 
faults
Check the following:
1.  Motor power (P0307) must correspond to
inverter power (r0206).
2.  Cable length limits must not be exceeded.
3.  Motor cable and motor must have no short-
circuits or earth faults
4.  Motor parameters must match the motor in
use
5.  Motor must not be obstructed or overloaded.
Ø Increase 
the 
ramp 
time
Ø  Reduce the boost level
OFF2
F0002
OverVoltage
Ø  Overvoltage can be caused either
by too high main supply voltage
or if motor is in regenerative
mode.
Ø  Regenerative mode can be
caused by fast ramp downs or if
the motor is driven from an active
load.
Check the following:
1.  Supply voltage (P0210) must lie within limits
indicated on the inverter rating plate.
2.  DC-link voltage controller must be enabled
(P1240) and parameterized properly.
3.  Ramp-down time (P1121) must match inertia
of load.
NOTE
Higher inertia requires longer ramp times
OFF2
F0003
UnderVoltage
Ø Main 
supply 
failed.
Ø  Shock load outside specified
limits.
Check the following:
1.  Supply voltage (P0210) must lie within limits
indicated on the inverter rating plate.
2.  Supply must not be susceptible to temporary
failures or voltage reductions.
OFF2
F0004
Inverter Over
Temperature
Ø Ventilation 
inadequate
Ø  Ambient temperature is too high.
Check the following:
1.  Pulse frequency must be set to default value
2.  Ambient temperature could be higher than
specified for the inverter
OFF2
F0005
Inverter I
2
t
Ø Inverter 
overloaded.
Ø  Duty cycle too demanding.
Ø  Motor power (P0307) exceeds
inverter power capability ( r0206).
Check the following:
1.  Load duty cycle must lie within specified
limits.
2.  Motor power (P0307) must match inverter
power (r0206)
OFF2
F0011
Motor Over
Temperature
I
2
t
Motor overloaded
Check the following:
1.  Load duty cycle must be correct
2.  Motor temperatur warning level  (P0604) must
match.
OFF1
F0041
Stator resistance measurement
failure
Ø  Check if the motor is connected to the
inverter.
Ø  Check that the motor data have been entered
correctly.
OFF2
F0051
Parameter
EEPROM Fault
Read or write failure while saving
non-volatile parameter.
Factory Reset and new parameterization
Change drive
OFF2
F0052
power stack
Fault
Read failure for power stack
information or invalid data.
Change drive
OFF2