Emerson 5400 User Manual

Page of 42
Manual Supplement 
00809-0500-4530, Rev AA
October 2010
1-31
Rosemount 5300/5400 Series
Emerson Process Management
FloBoss 107
Figure 1-10. Wiring Diagram for 
Connecting 5300/5400 Modbus to 
Emerson Process Management 
FloBoss 107
Table 1-20.  Parameter Values (in 
case of Emerson Process 
Management FloBoss 107)
The Input Register Base Number needs to be added to the Input Register 
address of the 5300/5400 transmitter. In this case, register 1300 needs to 
have 1300 entered as the address.
ABB TotalFlow
Figure 1-11. Wiring diagram for 
connecting 5300/5400 Modbus to 
ABB TotalFlow
Table 1-21.  Parameter Values (in 
case of ABB TotalFlow)
The Input Register Base Number needs to be added to the Input Register 
address of the 5300/5400 transmitter. In this case, register 1302 needs to 
have 1303 entered as the address etc.
RS-485
A
B
NC
NC
PWR
GND
MA
MB
POWER +
POWER  -
FloBoss 107
5300/5400  Modbus
Power Supply
+ 8 to + 30 Vdc 
(max. rating)
GND
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Conversion Code 66
Input Register Base Number
0
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1