Emerson 5400 User Manual
Manual Supplement
00809-0500-4530, Rev AA
October 2010
October 2010
1-33
Rosemount 5300/5400 Series
ScadaPack
Figure 1-14. Wiring Diagram for
Connecting 5300/5400 Modbus to
SCADAPack 32
Connecting 5300/5400 Modbus to
SCADAPack 32
Table 1-24. Parameter Values (in
case of SCADAPack 32)
case of SCADAPack 32)
The Input Register Base Number needs to be added to the Input Register
address of the 5300/5400 transmitter. In this case, register 1302 needs to
have 31303 entered as the address etc.
address of the 5300/5400 transmitter. In this case, register 1302 needs to
have 31303 entered as the address etc.
Kimray DACC 2000/3000
This table shows input types in Kimray IMI software and the corresponding
value. The communication port must be configured to use “Tank Levels”
protocol.
value. The communication port must be configured to use “Tank Levels”
protocol.
Table 1-25. Kimray Input Types and
Corresponding Values
Corresponding Values
RS-485 on COM1
1 +5 V
2 RX-
3 TX-
4 GND
5 RX+
6 TX+
7 Not Used
8 Not Used
2 RX-
3 TX-
4 GND
5 RX+
6 TX+
7 Not Used
8 Not Used
SCADAPack32
MA
MB
POWER +
POWER -
MB
POWER +
POWER -
5300/5400 Modbus
Power Supply
+ 8 to + 30 Vdc
(max. rating)
REF
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
Kimray Inp type
5300/5400 variable
Format
Tank Level1
PV
ddd.dd.alt. -dd.dd
Tank Level2
SV
ddd.dd.alt -dd.dd