Clearances
  1.  In selecting a location for installation, it is necessary to provide 
adequate  accessibility  clearances  for  servicing  and  proper 
installation.
  2.  The DV4T-59-1, 5" to 9" wall depth is the standard vent 
kit provided with the DV-55T. See Accessories Page 6 to 
order vent kits for wall depths of 8" to 12" or 12" to 19". 
The use of tubes not supplied by the manufacturer results 
in unsatisfactory performance.
  3.  The DV-55T can be attached to the wall or recessed into the 
wall up to 4 inches in depth but the minimum 5 inches vent/air 
intake system  wall  depth  must  be  maintained. Example: If 
furnace is recessed into the wall at a depth of 4 inches, the 
minimum wall depth must be 9 inches.
  4.  The wall in which the furnace is recessed has (0) zero clearance 
to the furnace sides and top. 
  5.  When using side discharge registers, SOR-1 or SOK-1, the 
furnace cannot be recessed into the wall. 
  6.  Clearance to sidewall or combustible material is 4 inches.
  7.  Ceiling clearance is 4 inches.
  8.  Floor and rear wall clearance is (0) zero inches.
  9.  Clearance of 18 inches is required to sidewall or combustible 
material when flush mounted SOR-1, side outlet register is 
used. See Figure 4.
 10.  The minimum distance from the center of the vent cap to the 
nearest outside corner or obstruction is 24 inches. 
The vent terminal of a direct vent appliance with an input over 
50,000 BTU per hour shall be located at least 12 inches from any 
opening through which flue gases could enter a building. The bot-
tom of the vent terminal and the air intake shall be located at least 
12 inches above grade. 
WARNING: The nearest point of the vent cap should be a 
minimum horizontal distant of six (6) feet from any pres-
sure regulator. In case of regulator malfunction, the six 
(6) feet distance will reduce the chance of gas entering the 
vent cap.
Figure 4  
Figure 3
Checking Manifold Pressure
Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 
regulator in the gas valve. Natural gas models will have a manifold 
pressure of approximately 4.0" w.c. at the valve outlet with the 
inlet pressure to the valve from a minimum of 6.0" w.c. for the 
purpose of input adjustment to a maximum of 7.0" w.c.  Propane 
gas  models  will  have  a  manifold  pressure  approximately  10.0" 
w.c. at the valve outlet with the inlet pressure to the valve from a 
minimum of 11.0" w.c. for the purpose of input adjustment to a 
maximum of 13.0" w.c. 
A 1/8" N.P.T. plugged tapping, accessible for test gauge connection, 
is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure 
and full on in 10 seconds.
CLEARANCES