Revision 0.07 
25 
3.3.3.4  Warning Set Point 
S  e  n  s  o  r    0  1          C O   
W a  r  n  i  n  g  :    _  _  5  0  p  p m 
Figure 3-27 Sensor’s Warning Level 
The default warning levels for the sensors are: 
– 
Carbon Monoxide 
50 ppm 
– 
Nitrogen Dioxide  
3.0 ppm 
– 
Combustible  
2,000 ppm (5% LEL for methane) 
 
Setting a warning level of 0 (zero) will disable warning detection for this particular sensor. 
3.3.3.5  Range 
S  e  n  s  o  r    0  1          C O   
R  a  n  g  e  :        _  2  0  0  p  p m 
Figure 3-28 Sensor’s Range 
The range for each sensor is the gas concentration that corresponds to the 20 mA signal level. 
 
The default range values for the sensors are: 
– 
Carbon Monoxide 
200 ppm 
– 
Nitrogen Dioxide  
6.0 ppm 
– 
Combustible  
10,000 ppm (25% LEL for methane)