3.3.5
  Configure Horn Submenu 
The configuration parameters for the horn are the same as those for relays. A horn would not normally require a 
minimum on time but this parameter allows a more versatile configuration. 
3.3.5.1  Horn Summary 
H o  r  n    4      N o  r  m  .  O  f  f 
D e  l  a  y    O n                 
Figure 3-33 Horn Summary 
This display example shows that the horn has been configured to operate Normally Off, with a turn on delay 
and no minimum on time. 
 
Notice that the horn number,  4, is underlined. This indicates that the digit keys can be used to jump to a 
particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5. 
3.3.5.2  Horn Mode 
H o  r  n          N o  r  m  .  O  f  f 
M o  d  e  :  2                     
Figure 3-34 Horn Mode 
This display example shows that the horn is configured to operate in the Normally Off mode. The valid modes 
are: 
– 
Normally Off (default) 
– 
Normally On 
 
3.3.5.3  Horn Turn On Delay 
H o  r  n          D e  l  a  y    O n 
(  m m  :  s  s  )    0  1  :  0  0       
Figure 3-35 Horn Turn On Delay 
The default turn on delay is one minute and the maximum allowed value is fifteen minutes. 
3.3.5.4  Horn Minimum On Time 
H o  r  n              M i  n  .  O n 
(  m m  :  s  s  )    0  0  :  0  0       
Figure 3-36 Horn Minimum on time 
The default minimum on time is zero and the maximum allowed value is fifteen minutes.