3.3.8.4  Alarm Strobe Signal 
A  l  a  r  m    S  i  g  n  a  l  s       
S  t  r  o  b  e  :  1    C o  n  t  i  n  . 
Figure 3-55 Strobe Alarm Signal 
This display example shows that the strobe will signal an alarm condition with a continuous signal. The signal 
definitions are: 
– 
Continuous (default) 
– 
Intermittent, one second on at two second intervals 
– 
Double Tap, two beeps at 5 second intervals 
– 
Triple Tap, three short beeps at 15 second intervals 
– 
Off, strobe will not flash  
 
3.3.8.5  Warning Signal Summary 
 
The warning signals are in response to one or more sensors indicating gas levels at or above the sensors’ 
configured warning level.  
W a  r  n  i  n  g    S  i  g  n  a  l  s   
B u  z  z                         
Figure 3-56 Warning Signals 
This display example shows that warnings are signaled by the internal Buzzer only. 
3.3.8.6  Warning Buzzer Signal 
W a  r  n  i  n  g    S  i  g  n  a  l  s   
B u  z  z  :  5                O F  F 
Figure 3-57 Buzzer Warning Signal 
This display example shows that the buzzer will not signal a warning condition. The signal definitions are: 
– 
Continuous 
– 
Intermittent, one second on at two second intervals 
– 
Double Tap, two beeps at 5 second intervals 
– 
Triple Tap, three short beeps at 15 second intervals 
– 
Off, buzzer will not sound  (default) 
3.3.8.7  Warning Horn Signal 
W a  r  n  i  n  g    S  i  g  n  a  l  s   
H o  r  n  :  5                O F  F 
Figure 3-58 Horn Warning Signal 
This display example shows that the horn will not signal a warning condition. The signal definitions are: 
– 
Continuous 
– 
Intermittent, one second on at two second intervals  
– 
Double Tap, two beeps at 5 second intervals 
– 
Triple Tap, three short beeps at 15 second intervals 
– 
Off, horn will not sound (default) 
3.3.8.8  Warning Strobe Signal 
W a  r  n  i  n  g    S  i  g  n  a  l  s