Macurco DVP-120 Manual De Usuario

Descargar
Página de 37
Revision 0.07 
34 
S  t  r  o  b  e  :  5            O F  F 
Figure 3-59 Strobe Warning Signal 
This display example shows that the strobe will not signal a warning condition. The signal definitions are: 
– 
Continuous  
– 
Intermittent, one second on at two second intervals 
– 
Double Tap, two beeps at 5 second intervals 
– 
Triple Tap, three short beeps at 15 second intervals 
– 
Off, strobe will not flash (default) 
3.3.8.9  Trouble Signal Summary 
 
The trouble signals are in response to one or more sensor faults, either as a defined current level, or because of 
wiring problems 
T  r  o  u  b  l  e    S  i  g  n  a  l  s   
B u  z  z                         
Figure 3-60 Trouble Signals 
This display example shows that troubles are signaled by the internal Buzzer only. 
3.3.8.10 Trouble Buzzer Signal 
T  r  o  u  b  l  e    S  i  g  n  a  l  s   
B u  z  z  :  4          T  r  i  p  l  e 
Figure 3-61 Buzzer Trouble Signal 
This display example shows that the buzzer will signal a trouble condition with a triple tap signal. The signal 
definitions are: 
– 
Continuous 
– 
Intermittent, one second on at two second intervals 
– 
Double Tap, two beeps at 5 second intervals 
– 
Triple Tap, three short beeps at 15 second intervals (default) 
– 
Off, buzzer will not sound  
3.3.8.11 Trouble Horn Signal 
T  r  o  u  b  l  e    S  i  g  n  a  l  s   
H o  r  n  :  5                O F  F 
Figure 3-62 Horn Trouble Signal 
This display example shows that the horn will not signal a trouble condition. The signal definitions are: 
– 
Continuous 
– 
Intermittent, one second on at two second intervals  
– 
Double Tap, two beeps at 5 second intervals 
– 
Triple Tap, three short beeps at 15 second intervals 
– 
Off, horn will not sound (default)