Instruction 3015-4275 
17 
AGM300 - Connecting External Alarms 
Overview 
The AGM300 includes 4 Form C SPDT alarm contacts for the connection of external alarm devices. The relays 
are factory assigned to the following conditions: 
 Relay 
#1 Leak 
 Relay 
#2 Spill 
 Relay 
#3 Evacuate 
 Relay 
#4 Fault 
 
Connection 
Use the AC conduit or any of the remaining service knockouts to gain cable access to the interior of the 
monitor. Locate the relay connector (Page 7) and remove it from the circuit board. Secure the leads to the 
connector orienting them as shown in the diagram below. When you are through securing the connections, 
carefully plug the connector back onto the circuit board. 
 
AGM300 Relay Connector 
 
 
 
 
 
 
 
 
 
NOTE:  Each relay may be connected as normally open (NO), or normally closed (NC). 
Latching / Non-Latching – refer to Page 38 to select Alarm Ack Mode. 
Alarm power source – power for the alarm devices connected to the relay contacts may be supplied from the 
Auxiliary AC Power Out Connector, 5 amp. max. (Page 7).