Parallel Compressor Systems Installation & Operations Manual, October 2004  
29
Parallel Compressor Systems
Suction Filter
Replaceable  core  suction  filters  are  supplied  as  standard 
on  all  units. The  flanged  shell  holds  replaceable  pleated 
filter elements suitable for installation in the suction line of 
refrigeration systems. In this way any contaminants left in the 
system at start-up can be removed before they circulate back 
to the compressor. The suction filters are shipped loose for 
field installation. (See No. 3 of Leak Checking, Evacuation,  and 
Start-up section in this manual).
Compressor Motor Burnout Cleanup Procedure
Another benefit of the suction filter is its use in cleanup of a 
system after a burnout. Standard liquid cores can be installed in 
the shell to aid in the cleanup of acids and other contaminants 
from a motor burnout. 
The  following  procedure  can  be  used  in  case  of  a  motor 
burnout.
1.   Determine the extent of the burnout. For mild burnout’s 
where contamination has not spread through the system, 
it may be economical to save the refrigerant. Normally 
it is economical to save the refrigeration charge if the 
system has service valves. A severe burnout exists if the oil 
is discolored, an acid odor is present and contamination 
products are found in the high and low side. With this 
condition, extreme caution should be exercised to avoid 
breathing the acid vapors and to prevent contaminated 
liquid from making contact with the skin.
2.   Thoroughly clean and replace all system controls, such 
as expansion valves, solenoids, check valves, reversing 
valves, oil separators, suction accumulators, etc. Remove 
all strainers and filter-driers.
3.   Install a replacement compressor and make a complete 
electrical check.
4.   Make sure the suction line adjacent to the compressor 
is clean. Install a liquid line filter-drier or a replaceable 
cartridge  designed  for “cleanup”  into  the  suction  line 
shell.
5.   Install a burnout core in the liquid line shell.
6.   If the refrigerant is removed from the system, follow the 
evacuation procedure found on page 17 of this manual.
7.   Start the compressor and put the system in operation. 
Record the pressure drop across the suction line filter and 
keep for reference.
8.   Replace the suction line filter-drier blocks if the pressure 
drop becomes excessive.
9.   Observe the system during the first 4 hours. Repeat step 
8 as often as required, until no further change in pressure 
drop is observed.
10.   After the system has been in operation for 48 hours, check 
the condition of the oil for Acids. If the oil test indicates an 
acid condition, replace the liquid and suction line filter-
driers.
11.   Check the system again after approximately 2 weeks of 
operation. If the oil is still discolored, or checks acid, replace 
the liquid and suction line filter-driers.
12.   Cleanup is complete when the oil is clean, odor free, and is 
determined to be acceptable by testing for acids or other 
contaminants. 
13.   Replace the suction line filter-drier with suction line filters 
cores to minimize suction line pressure drop and to provide 
maximum compressor protection.
For more detailed information on burnout cleanup procedures 
and  recommendations,  consult  the  RSES  Service  Manual, 
section 91.
Sporlan Valve Company
Replaceable Suction Filter
The correct replacement suction filter element in Sporlan Valve 
replaceable shells is Sporlan part number RFE-48-BD. However 
any suitable filter that is sized to fit a 48 cu. inch vessel will 
substitute.