Siemens NCM S7 Manual De Usuario
NCM S7 Diagnostics
215
SIMATIC NET NCM S7 for Industrial Ethernet
Release 6/2003
Release 6/2003
C79000–G8976–C129–07
7.3.4
Using a Gateway
Case a: One gateway
If the CP you want to check with diagnostic functions can only be reached via a
gateway, you must select the device and specify its node address in the local
network.
gateway, you must select the device and specify its node address in the local
network.
You must also specify the S7 subnet ID of the destination network:
The subnet ID consists of two numbers separated by a dash:
– One number for the project
– One number for the subnet
You will find the subnet ID in the object properties of the subnet in the STEP 7
project. The subnet ID is also printed out with the network configuration.
project. The subnet ID is also printed out with the network configuration.
Node address: PRO-
FIBUS address 9
Rack / slot : 0/5
S7 – 300
CP
U
U
C
P
P
PG/PC
C
P
P
Attachment of gateway:
Industrial Ethernet
S7 – 300
CP
U
U
C
P
P
Node address (gateway) (MAC):
08-00-06-01-02-03
Attachment of target sta-
tion : MPI/PROFIBUS/AUTO
S7 subnet ID of target network:
0001 0001
Figure 7-3
Example of the Parameter Settings for the Online Path with one Gateway