Stabilization of Unstable Control Loops 
 
 
14 
MPC Level 
V 1.0, Beitrags-ID: 42200753 
 
C
opyr
ight 
 Si
em
ens
 AG 2
010
 Al
l r
ights r
es
er
ved 
3.2 
PID Tuner 
The PCS 7 PID tuner can be used for integral processes without problems if at 
least one stable controller parameterization is already available. The following hints 
are helpful for this: 
  Fix the check mark „With integral action in the process“ 
  Excite the process with a step in the set point in closed loop in automatic mode 
  Chose the proportional only controller as controller type, at least, if you want to 
use this controller as slave controller in cascades (e.g. subordinated to a MPC) 
or if you are not interested in exact set point tracking. 
  Set the MC_Offset to the value of the manipulated variable needed to reach 
the typical operating point, if you know it, in order to avoid the persistent control 
error at least in this operating point.