Configuration of MPC with Slave Controller
 
MPC Level 
V 1.0, Beitrags-ID: 42200753 
15
 
C
opyr
ight 
 Si
em
ens
 AG 2
010
 Al
l r
ights r
es
er
ved 
Configuration of MPC with Slave 
Controller 
4.1 
Starting Point 
The starting point is the standard connection of the MPC with its actuators. The 
structure of the following example corresponds to the control of product quality 
(CV1) and level (CV2) in a reactor as mentioned in section 2.3.4. However, this ex-
ample is not a realistic simulation of a real reactor. 
 
Figure 4-1 Original signal flow chart of an MPC with 2x2 process, where the main transfer 
function g22 shows an integral action 
g22
g21
g12
g11
ModPreCon
.
MV1
MV2
CV1
CV2
CV2
g22
g21
g12
g11
ModPreCon
.
MV1
MV2
CV1
CV2
CV2
 
 
4.2 
Connection in CFC 
Now, a stabilizing PID controller is inserted for the integral sub process. In principal 
this control structure is a cascade consisting of an MPC as master controller and 
the stabilizing proportional-only controller as slave. The external set point SP_EXT 
of the slave controller is linked to the corresponding manipulated variable of the 
MPC. 
The equality of the controlled variable of the master controller (i.e. the correspond-
ing MPC control channel) and the controlled variable of the slave controller is the 
only special feature in the present case.