PW-6000 Installation
Setting Up the PW-6000 Hardware
PW-6000 Installation Guide, Document 800-00005, Revision A
13
Run TimeSupplying Power to the PW-6000 Interface
3.5 Supplying Power to the PW-6000 Interface
The processor accepts 12Vdc for power. Locate power source as close to the unit as possible and
connect it with minimum of 18AWG wires.
connect it with minimum of 18AWG wires.
Caution:
Observe POLARITY on 12 VDC.
Figure 2: PW-6000 Power Terminals
Table 5 PW-6000 Status LED Combinations During Run Time
LED
Description
1
Off-Line / On-Line and Battery Status
Off-Line = 20% On, ON-Line = 80% On
Double Flash means the Battery is Low
2
Primary Host Communication Activity (Ethernet or Port 1)
3
Port 2 Communication Activity
4
Port 3 Communication Activity
5
ON = Writing to Flash Memory. Do NOT cut off power when this LED is ON.
6
TBD
SPD
On-Board Ethernet Speed. OFF = 10MBS. ON = 100MBS.
ACT
OFF = No On-Board Ethernet Activity. ON = On-Board Ethernet Activity
(YELLOW LED).
(YELLOW LED).
LNK
OFF = ON Link. ON = Good Link (GREEN LED).
PORT 3
+12V
GND
-
+
TB1
GND
TR-
TR+
12Vdc ±10%