Honeywell PW-6000 Manual De Usuario

Descargar
Página de 36
PW-6000 Installation
Setting Up the PW-6000 Hardware
PW-6000 Installation GuideDocument 800-00005, Revision A
11
3.3  Technical Specifications
Table 3  PW-6000 Technical Specifications
Category
Description
WARNING: PW-6000 is manufactured for use in 
low-voltage, Class 2 circuits only.
Primary Power
12Vdc ± 10%, 300mA maximum.
12Vdc @ 240mA (325mA with CoBox-Micro) nominal.
Memory and 
Clock Backup
3Volts Lithium, type BR2325, BR2330, CR2330.
Ports
Port 0 10Base-T/100Base-TX 
Ethernet.
Port 1 
RS-232 or 2-wire RS-485: 9,600 to 115,200 
bps, async. An optional Lantronix 
CoBox-Micro interface daughter board is 
supported (10Base-T/100Base-TX). 
Port 2 & 3 
2-wire RS-485: 2,400 to 38,400 bps, async.
Inputs
2 non-supervised, dedicated for cabinet tamper and power fault 
monitoring.
Cable requirements
Power: 
1 twisted pair, 18 AWG.
RS-485: 
24AWG, 4,000ft (1,200m) maximum, twisted 
pair with shield. 120 ohm. 
RS-232: 
24AWG, 25ft (7.6m) maximum. 
Ethernet: Cat 
5. 
Alarm input: 
1 twisted pair, 30 ohms maximum. 
Environmental
Temperature:  0 to 50°C, operating 
-55 to +85°C, storage 
Humidity: 
0 to 95% RHNC 
Mechanical
Dimensions: 
5.5 in. (137.7mm) W x 9 in. (228.6.4mm) L 
x .75 in. (19.05mm) H 
Weight: 
7.1 oz. (201 gm) nominal 
Lantronix NIC 
support
Standoff size 
Diameter 0.125 inch x 0.4375 inch long 
Richco Plastics part number LMSP-7-01, 3 pieces (not 
supplied) 
Specifications subject to change without notice.