AEG 1000 Manual De Usuario

Descargar
Página de 76
 
 
51 
EN 
Description Adjustable 
parameters 
Presetting 
Automatic 
Start Delay 
[Off], [On] = <hh>H <mm>M <ss>S 
Adjustment: Hours, Minutes, Seconds
 
<00>H <00>M <00>S
  to  
<12>H <59>M <59>S
 
If Off, automatic restart is disabled on 
the selected load segment and turns 
on only when commanded manually by 
on/off select button or via the display 
(Control => Load Segments) 
Load 
Segment <1> 
1s,  
Load 
Segment <2> 
2s 
Automatic  
on Battery 
Shutdown  
 
[Off], [On] = <hh>H <mm>M <ss>S 
Adjustment: Hours, Minutes, Seconds
 
<00>H <00>M <00>S
  to  
<12>H <59>M <59>S
 
 
 
Load 
Segment <1> 
Off,  
Load 
Segment <2> 
Off 
To control the load segments with power management software, see 
your power management software manual for details. Refer to the 
software “CompuWatch” (included on CD) or www.aegpartnernet.com 
for latest information. 
To control the load segments through the display: 
1.   Press “ESC” button to activate the menu options, and then select 
CONTROL and LOAD SEGMENTS. 
2.   Set the desired load segment ON or OFF, and ENTER to confirm. 
3.   Set the other load segment if applicable. 
To set the restart and shutdown delay times for each load segment: 
1.   Press “ESC” button to activate the menu options and then select 
SETTINGS, and AUTOMATIC START DELAY. 
2.   Set the restart delay for one load segment, and ENTER to confirm. 
3.   Set the other load segment if applicable. 
4.   Select AUTOMATIC ON BATTERY SHUTDOWN. 
5.   Set the shutdown delay for one load segment, and ENTER to 
confirm. 
6.   Set the other load segment if applicable. 
i
 
Load segment On/Off commands issued through the 
Control menu overrules the settings for load segments
.