Description Adjustable 
parameters 
Presetting 
Ambient 
temperature 
high alarm 
[enabled], [disabled] 
 
If enabled, UPS alarm when ambient 
temperature >40°C 
enabled  
EPO 
operation 
[normally open], [normally closed] 
Normally open means UPS makes a 
shutdown by a closing input state. 
Normally closed means UPS makes a 
shutdown by an opening input state. 
Setting only available in UPS stand-by 
mode. 
normally 
closed 
Reset 
Cumulative 
Consumption 
kWh  
 
[no], [yes] 
If “no”, no action. 
If “yes”, the Cumulative Consumption 
kWh value is cleared and the date and 
time stamp for this statistic is set to the 
current date and time. 
no 
 
Battery limit 
time 
5h,
 
6h,
 
...14h,
 
15h,
 
16h,
 
…999h, disabled 
Default “14h” means when work on  
battery mode for more than 14 hours,  
UPS will make bat low alarm and then 
shutdown itself 30 minutes later even 
battery voltage still above the 
shutdown value.  
Disabled means “No time limitation”   
for battery mode 
14h 
Auto reboot 
[enabled], [disabled] 
 
Enabled means UPS will auto restart 
to normal mode while utility recover 
after the UPS has been shutdown for 
battery low. 
enabled 
The UPS automatically restarts if utility returns after the output was shut 
off due to exhausted batteries, a shutdown input signal, or automatic 
shutdown command. 
You can set the load segment for the amount of time to delay the restart 
once utility returns, using the “Automatic Start Delay” setting. You can 
also configure UPS restart to depend on the battery charge level, using 
the “Battery Charge Capabilitiy % to Restart” setting.