Set Up and Calibration Procedures 
Input Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
41 
7/08  
 
 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink Prompt 
 
FSFTYPL 
 
 
 
 
 
 
 
LAST 
UP 
DOWN 
USER 
 
default = DOWN 
FAILSAFELO TYPE
—Selects the motor position you want 
the actuator to go to when input signal is below the low end 
range value or on loss of input signal. 
NOTE:  Failsafe condition occurs when the input exceeds its 
low end range value by 3%, or when the input signal goes to 
zero. For input types 0 to 20mA, 0 to 5 V, and 0 to 10 V 
there is no failsafe condition at the zero value. 
Last Position
—Actuator motor remains at last position. 
Up
—Actuator motor moves to full scale value. 
Down
—Actuator motor moves to zero value. 
User selected value
—Actuator motor moves to a customer-
defined value.   
Allows setting of failsafelo input value. 
 
FsFVALL * 
0
 to 100% 
 
 
default = 0
 
FAILSAFELO INPUT VALUE
—(FailsafeLO Type USER 
only) Selects the motor position you want the actuator to go 
to when input signal is below the low end range value or on 
loss of input. 
Range is from 0 to 100%.   
CHAR 
LINR 
SQRT 
CUST 
 
 
 
default = LINR 
 
 
INPUT CHARACTERIZATION
 Selects a characterization 
type that causes the actuator to characterize a linear input 
signal to represent a non-linear input.   
Linear
— Provides linear characterization of the input signal.  
Square Root
 Provides square root characterizations of 
the input signal.  
Custom
— Custom characterization.  Selecting custom 
allows you to create a twentieth order characterization of 
input value (x) and associated shaft position (y).   
NOTE:  Selecting CUST input characterization causes the 
following prompt CUSTOM to be displayed.  
CUSTOM 
EQUL 
QUIK 
USER 
 
default = EQUL 
 
Equal percentage – 
Sets the characterization as explained 
in Equal Percentage Valve Characteristic on page 42. 
Values are read-only. 
Quick opening 
- Sets the characterization as explained in 
Quick Opening Valve Characteristic on page 43. Values are 
read-only. 
User-configurable 
– Lets you create your own 
characterization using the following Xn VAL and Yn VAL 
prompts. 
Xn VAL 
n = 1 - 20 
0 to 100 % 
Input Value
 as a percentage of input range.  Defaults are 
in increments of 5%. 
Yn VAL 
n = 1 - 20 
0 to 100 % 
Shaft Position Value
 as a percentage of position range. 
Defaults are in increments of 5%.