Set Up and Calibration Procedures 
Input Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
43 
7/08  
 
 
Quick Opening Valve Characteristic 
Table 12 contains values that approximate the characteristic of a quick opening control valve. When the 
QUIK custom characterization type is selected, the values in Table 12 are automatically loaded into the 
actuator configuration to produce the characteristic as presented in the graph.  The Xn VAL is the input 
value as a percentage of range and Yn VAL is the characterized output (actuator shaft position) as a 
percentage of range.  
Table 12 Quick Opening Valve Characteristic 
 
Order 
Xn VAL 
% of 
Range 
Yn Val 
% of 
Range 
 
Quick Opening Valve Characteristic 
0 0  0 
1 5  10 
2 10  20 
3 15  30 
4 20  40 
5 25  50 
6 30  60 
7 35  70 
8 40  77 
9 45  82 
10 50  86 
11 55  88 
12 60  90 
13 65  92 
14 70  94 
15 75  95 
16 80  96 
17 85  97.5 
18 90  98.5 
19 95  99.5 
20 100  100 
 