Set Up and Calibration Procedures 
Relays Set Up Group 
46 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Relay connector #1
Relay connector #2
Relay connector #3
Relay connector #4
 
Figure 22 Relay connectors 
Relay Examples 
Relay Type - Position Range  
Selecting PosR relay type, you can cause the relay to energize when the actuator motor travels below 20% 
of range and above 80% of range. Note in the example below that Relay 1 is set up to provide two trip 
points.  The first trip point (R11VAL) causes the relay to energize when the motor travels above 80%, the 
second trip point (R12VAL) is set so the relay energizes when the motor travels below 20%.  
Set Up Group 
Parameter 
Value 
SET RELAY1 
RTYP11 
PosR 
 R11VAL 
80.0 
 R11HL 
HI 
 RTYP12 
PosR 
 R12VAL 
20.0 
 R12HL 
LO 
 RLY1HY 
0.0 
The figure below shows the resulting action.   
100%
0%
18
Closed
20%
80%
RELAY 1
Normally Open
Closed
Open
Motor
Position
17
18
17