Set Up and Calibration Procedures 
Relays Set Up Group 
44 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Relays Set Up Group 
 
 
ATTENTION 
The Relay set up group parameters are accessible only if relay PWAs are installed in the 
actuator.  HercuLine
®
 2001 actuators can be equipped with one PWA –for a total of two SPDT 
relays. Using the Relay set up groups you can program the installed relays to operate in 
response to various operating conditions.  
 
Table 13 lists the parameters and selections available when the SET RELAYn group is selected. 
Table 13 Relay Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink
®
 Prompt 
RTYPny 
n
 = 1, 2, 3, or 4 
= 1 or 2 
 
NONE 
 
InPR 
PosR 
 
DEV 
ULim 
LLim 
T Hi 
T Lo 
STRT 
 
STAL 
MAN 
PWRF 
FsFA 
PosF 
 
DiGI 
TDEG 
default = InPR and 
NONE 
RELAY TYPE
— Selects the relay number and the relay 
activation type.  See Table 14 Relay Type Descriptions. 
Input Range
 Upper / lower limits of input signal exceeded 
Position Range
— Upper / lower limits of motor position 
exceeded 
Deviation
— Deviation from input exceeded 
Upper Limit Travel
— Same as PosR for upper limit 
Lower Limit Travel
 Same as PosR for lower limit 
Temperature High
— High temperature limit exceeded 
Temperature Low
 Low temperature limit exceeded 
Starts
— Motor starts limit exceeded.  Allows setting of 
multiplier value.   
Stalled
  Motor position does not follow input 
Manual
— Actuator is set to manual mode 
Power Up Test Failure
— Failure of any power up diagnostic
Failsafe Alarm
 Failsafe condition detected  
Position Sensor Signal Failure
 position output out of valid 
range 
Digital Input
— Digital input closure 
Total Degrees
 total degrees traveled. Allows setting of 
multiplier value. 
RnyE* 
X1 
 X10k 
default = X1 
MULTIPLIER
— (Relay Types STRT and TDEG only) 
Selects the multiplier for the number limit of motor starts and 
total degrees traveled before the relay is activated.  Multiplier 
specifies the value on display as times one (X1) or times ten 
thousand (X10k).  
RnyVAL 
n
 = 1, 2, 3, or 4 
= 1 or 2 
0.0 to 100.0 
RELAY VALUE
— Sets numerical value of limit where relay 
trips (energizes).  Units are determined by the relay type 
selection. See Table 14 Relay Type Descriptions for units. 
Rny HL 
n
 = 1, 2, 3, or 4 
= 1 or 2 
HI 
 LO 
RELAY HIGH/LOW
— Sets relay trip point to high or low 
limit.  
RLYnHY 
n
 = 1, 2, 3, or 4 
0.0 to 100.0 
(in percent) 
RELAY HYSTERESIS
— 0.0 to 100.0% of span or full output.
NOTE:  Relay Hysteresis parameter is accessible only if 
appropriate relay type is selected.   
n
 is the relay number, y is the relay contact.