Set Up and Calibration Procedures 
Calibration 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
77 
7/08  
 
 
 
Potentiometer position sensor
Mounting bracket
 
Figure 29 Location of potentiometer position sensor 
 
Table 31 Load Position Sensor Factory Calibration 
Step 
Action 
Reapply AC power to the actuator.  
Press SET UP key to access the MAINT set up group.  Press the FUNCTION key until the 
display reads LD CAL.  
Press the 
 or 
 keys until the display reads POS. 
Perform the Calibrate Motor procedure exactly as in Table 26  Motor calibration must be 
performed for the factory configured full span range (0-100%).   
ATTENTION 
When calibrating the motor to a short stroke range, you must reset the end-of-travel limit 
switches.  See Setting End-of-Travel Limit Switches
When motor calibration is complete, the calibration is now stored as the factory calibration of 
the actuator motor.