Honeywell herculine 2000 ユーザーズマニュアル
Set Up and Calibration Procedures
Calibration
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
77
7/08
Potentiometer position sensor
Mounting bracket
Figure 29 Location of potentiometer position sensor
Table 31 Load Position Sensor Factory Calibration
Step
Action
1
Reapply AC power to the actuator.
2
Press SET UP key to access the MAINT set up group. Press the FUNCTION key until the
display reads LD CAL.
display reads LD CAL.
Press the
or
keys until the display reads POS.
3
Perform the Calibrate Motor procedure exactly as in Table 26 Motor calibration must be
performed for the factory configured full span range (0-100%).
performed for the factory configured full span range (0-100%).
ATTENTION
When calibrating the motor to a short stroke range, you must reset the end-of-travel limit
switches. See Setting End-of-Travel Limit Switches.
switches. See Setting End-of-Travel Limit Switches.
4
When motor calibration is complete, the calibration is now stored as the factory calibration of
the actuator motor.
the actuator motor.