Bard CH4S1 Manual De Usuario

Descargar
Página de 28
Manual 2100-455M 
Page  16 of 28
lOW VOltaGe cOnnectIOns
These units use a grounded 24 volt AC low voltage 
circuit and require at least a 2 stage heating and a 2 
stage cooling thermostat.  
“G” terminal is the fan input.
“Y” terminal is the compressor Stage 1 input.
“Y1” terminal is the compressor Stage 2 input.
“B” terminal is the reversing valve input.  The 
reversing valve must be energized for heating mode.
“R” terminal is 24 VAC hot.
“C” terminal is 24 VAC grounded.
“L” terminal is compressor lockout output.  This 
terminal is activated on a high or low pressure trip by 
the electronic heat pump control.  This is a 24 VAC 
output.
“W2” terminal is second stage heat (if equipped).  
“O1” terminal is the ventilation input.  This terminal 
energizes any factory or field installed ventilation 
option.
“DH” terminal is the 
dehumidifier input.  This terminal 
energizes the factory or field installed dehumidifier 
option.
“E” terminal is the emergency heat input.  This 
terminal energizes the emergency heat relay if 
equipped.
NOTE:  For total and proper control using DDC, a 
minimum of 8 controlled outputs are required 
(6 if no ventilation or dehumidifier option
is installed).  For proper system operation 
under Emergency Heat conditions where
the compressor needs to be deactivated, 
the B-W2-E outputs need to be energized.  
Removing the Y (compressor) signal alone 
turns the compressor off, but does not activate 
the additional circuitry embedded in the heat 
pump for proper and complete operation.
lOW VOltaGe cOnnectIOns
FOr DDc cOntrOl
  Fan Only 
 
Energize G
 
  Cooling Mode 1st Stage 
 
Energize Y, G
 
  Cooling Mode 2nd Stage 
 
Energize Y, Y1, G
 
  Heat Pump Heating 1st Stage  Energize Y, G, B
  Heat Pump Heating 2nd Stage  Energize Y, Y1, G, B
 
  3rd Stage Heating  
 
Energize G, W2, Y, B, Y1
  w/Heat Pump (if employed) 
 
Ventilation 
 
Energize G, O1
 
Dehumidifier 
 
Energize DH
 
 
Emergency Heat 
 
Energize B, W2, E, G
start uP
These units require R-410A refrigerant & Polyol Ester oil.
aPPlIcatIOn:
1.  Use separate service and manufacturing equipment  
 
to avoid cross contamination of oil and refrigerants.
2.  Use recovery equipment rated for R-410A  
 
 refrigerant.
3.  Use manifold gauges rated for R-410A (800 psi/250  
 
psi low).
4.  R-410A is a binary blend of HFC-32 and HFC-125.
5.  R-410A is nearly azeotropic - similar to R-22 and  
 
R-12.  Although nearly azeotropic, charge with   
 
liquid refrigerant.
6.  R-410A operates at 40-70% higher pressure than   
 
R-22, and systems designed for R-22 cannot  
 
 
withstand this higher pressure.
7.  R-410A has an ozone depletion potential of zero,  
 
but must be reclaimed due to its global warming  
 potential.
8.  R-410A compressors use Polyol Ester oil.
9.  Polyol Ester oil is hygroscopic; it will rapidly    
 
absorb moisture and strongly hold this moisture in  
 
the oil.
10. A liquid line dryer must be used - even a deep    
 
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes -  
 
 
MAxIMuM.
12. If compressor removal is necessary, always plug  
 
compressor immediately after removal.  Purge    
 
with small amount of nitrogen when inserting plugs.