Bard CH4S1 Manual De Usuario

Descargar
Página de 28
Manual 2100-455M 
Page 
17 of 28
start uP cOnt’D.
saFetY PractIces:
1.  Never mix R-410A with other refrigerants.
2.  Use gloves and safety glasses, Polyol Ester oils can  
 
be irritating to the skin, and liquid refrigerant will  
 
freeze the skin.
3.  Never use air and R-410A to leak check; the  
 
 
mixture may become flammable.
4.  Do not inhale R-410A – the vapor attacks the    
 
nervous system, creating dizziness, loss of  
 
 
coordination and slurred speech.  Cardiac  
 
 
irregularities, unconsciousness and ultimate death  
 
can result from breathing this concentration.
5.  Do not burn R-410A.  This decomposition produces  
 
hazardous vapors.  Evacuate the area if exposed.
6.  Use only cylinders rated DOT4BA/4BW 400.
7.  Never fill cylinders over 80% of total capacity.
8.  Store cylinders in a cool area, out of direct sunlight.
9.  Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge  
 
lines or cylinders.  R-410A expands significantly at  
 
warmer temperatures.  Once a cylinder or line is full  
 
of liquid, any further rise in temperature will cause  
 
it to burst.
ImPOrtant Installer nOte
For improved start-up performance, wash the indoor coil 
with a dish washing detergent.
Pressure serVIce POrts
R-410A requires high pressure hose connections 
and gauges.  High and Low pressure service ports 
are installed on all units so that the system operating 
pressures can be observed.  Pressure tables can be found 
later in the manual covering all models on both cooling 
and heating cycles.  It is imperative to match the correct 
pressure table to the unit by model number.
hIGh & lOW Pressure sWItch
All models are supplied with a remote reset high and low 
pressure switch.  If tripped, this pressure switch may be 
reset by turning the thermostat off then back on again.
High/Low Pressure control provides protection for the 
compressor.  In the event system pressures go above 575 
PSI or below 32 PSI, in either cooling or heating mode, 
the compressor will be stopped.  This high pressure switch 
is located on the discharge line and is matched with Bard 
Part #8406-113.  This will activate the “L” terminal of 
the low voltage terminal strip.  This terminal can be used 
for remote indication of a pressure lockout.  The lockout 
circuit will hold compressor off line.  When the system 
problem is corrected, the unit operation can be restored 
by turning the main power supply off and then back on, or 
reset the room thermostat.  The low pressure control has a 
bypass circuit built into the Defrost Control Board.
three Phase scrOll cOmPressOr 
start uP InFOrmatIOn
Scroll compressors, like several other types of 
compressors, will only compress in one rotational 
direction.  Direction of rotation is not an issue with 
single phase compressors since they will always start 
and run in the proper direction.
However, three phase compressors will rotate in either 
direction depending upon phasing of the power.  Since 
there is a 50-50 chance of connecting power in such 
a way as to cause rotation in the reverse direction, 
verification of proper rotation must be made.  All three 
phase units incorporate a phase monitor to ensure proper 
field wiring.  See the “Phase Monitor” section later in 
this manual.
Verification of proper rotation must be made any time a 
compressor is changed or rewired. If improper rotation 
is corrected at this time there will be no negative impact 
on the durability of the compressor. However, reverse 
operation for over one hour may have a negative impact 
on the bearing due to oil pump out.
NOTE:  If compressor is allowed to run in reverse
rotation for several minutes, the compressor’s 
internal protector will trip.
All three phase ZR3 compressors are wired identically 
internally.  As a result, once the correct phasing 
is determined for a specific system or installation, 
connecting properly phased power leads to the same 
Fusite terminal should maintain proper rotation direction.
Verification of proper rotation direction is made by 
observing that suction pressure drops and discharge 
pressure rises when the compressor is energized.  Reverse 
rotation also results in an elevated sound level over that 
with correct rotations, as well as substantially reduced 
current draw compared to tabulate values.
The direction of rotation of the compressor may be 
changed by reversing any two line connections to the unit.