AEG Protect D. 6000 6000008439 Manual De Usuario

Los códigos de productos
6000008439
Descargar
Página de 4
2
Classification VFI SS 211 acc. to IEC 62040-3
D. 1000
D. 1500
D. 2000
D. 3000
Power type rating
1000 VA
1500 VA
2000 VA
3000 VA
900 W
1350 W
1800 W
2700 W
Part number  
(UPS including integrated battery system)
600 000 8434
600 000 8436
600 000 8437
600 000 8438
Part number (additional battery pack)
600 000 8441
600 000 8442
600 000 8443
UPS InPUt
Input voltage
220 V AC / 230 V AC / 240 V AC
Voltage range without battery mode  
(load dependent)
120 – 276 V AC
140 – 276 V AC
Frequency (auto selection)
50 Hz / 60 Hz ± 5 Hz
Mains current (system reaction)
λ ≥0.99 (THDi ≤8 %)
Current consumption at nominal load (max.)
4.8 A
7.2 A
9.6 A
13.7 A
UPS oUtPUt
Rated output voltage (adjustable)
200 V AC / 208 V AC / 220 V AC / 230 V AC (default) / 240 V AC ±2%
Frequency in battery- /  
frequency converter mode
50 Hz / 60 Hz ±0.25 Hz
output current (at 230 V AC)
4.3 A
6.5 A
8.7 A
13 A
transfer time at mains outage
0 ms (without interruption)
Voltage waveform
Sinusoidal, distortion THD <3 %
overload response (double conversion mode)
<130 % for 5 min. / 130 % – 150 % for 15 s
overload response (battery mode)
<130 % for 12 s / 130 % – 150 % for 2 s
Crest factor
3 : 1
Short circuit response
Short circuit proof (4 x I
N
 for 100 ms)
BAttERy
type
Sealed, maintenance free (proprietary brand), integrated, hot swappable
Rated voltage (linked)
36 V DC
48 V DC
72 V DC
Battery management
Temperature compensated with discharge protection,  
automatic battery test (programmable) and battery pack detection
Charging time (to 90 % rated capacity)
3 h
CoMMUnICAtIon
Interfaces (dual monitoring)
RS232, USB, communication slot (can be used parallel with RS232 / USB),  
input contact for emergency shutdown, programmable potential free contact
Shutdown software (on CD)
5 network licenses for all common OS (e.g. Windows, Linux, Mac, Unix, Sun etc.)
Failure indicators (acoustic /visual)
3 LED’s with traffic light display, detailed indication via LCD display  
(alarms: at mains failure, overload, battery charging, battery replacement, fan fault,  
data logger – with clear text display incl. date and time history)
GEnERAl DAtA
Efficiency (ECo+ mode)
>95 %
>98 %
Efficiency at nominal load  
(double conversion mode)
≥88 %
>88 %
>89 %
≥90 %
Audible noise (1 m distance)
<44 dB(A)
< 45 dB(A)
<52 dB(A)
operating temperature range
0°– 40 °C
Humidity
0 – 95 % (without condensation)
operation altitude
Up to 3000 m at nominal load
EMC conformity
EN 62040-2 Class C1, EN 61000-3-2, EN 61000-3-3
Product safety
EN 62040-1
number of outputs (switchable)  
automatically locked
6 x IEC 320 C13 (2+2)
8 x IEC 320 C13 (2+2)
6 x IEC 320 C13 (3+3)  
+ 1 x IEC 320 C19
Housing
Blackline metal case with aluminum front
Dimensions approx. W x H x D (mm) UPS
482.6 (19") x 88 (2 U) x 430
482.6 (19") x 88 (2 U) x 600
Dimensions approx. W x H x D (mm) battery 
482.6 (19") x 88 (2 U) x 430
482.6 (19") x 88 (2 U) x 430
Weight approx. UPS incl. integrated battery 
16 kg
19.5 kg
19 kg
29.5 kg
Weight approx. battery extension unit 
23 kg
28 kg
41 kg
41 kg
Shipment
Mains input cord (1 x EU, 1 x UK), UPS management software “CompuWatch” (CD),  
communications cables (RS232 & USB), operating instructions, rack rails,  
device cables: 3 x IEC 320 C13 (D. 1000 – D. 2000), 3 x IEC 320 C13 +1 x IEC 320 C19 (D. 3000)
Conformity
CE