4.2 Operating Mode 
  Normal range mode: Under Input mode the UPS accepts AC input voltage 
range for +/-20%.   
  Generator mode: Under generator mode, the low frequency transfer point can 
go as low as 40Hz and as high as 70Hz before being transferred to battery 
mode. 
  Wide range mode: Under Input settings mode, the UPS accepts AC input 
voltage range for -30% ~ +20%. 
  Battery mode 
When the UPS is operating during a power outage, the alarm beeps once every 
four seconds and the LCD display string shows “bATT” to indicate the UPS work 
at battery mode. 
If battery volume becomes low while in Battery mode, the alarm beeps once 
every second and the LCD display string shows “bATL”.   
  Standby mode 
When the UPS is turned off and remains plugged into a power outlet, the UPS is 
on Standby mode. The LCD display string shows “STbY” to indicate that power is 
not available to your equipment. The battery recharges when necessary.   
 
4.3 Configuring Load Segment 
Load segment are sets of receptacles that can be controlled through the display. 
Each UPS has two configurable load segments. See “Rear Panels” on page 30 
for load segment for each UPS model. 
 
Note: This configuring can be operated when UPS is power on.   
1 KVA E-model has only one load segment,can not configure. 
 
To configure the load segment through the display: 
1.  Enter settings mode: Press and hold the Enter button
 
 
more than 3 
seconds. Then UPS will transfer to setting mode. 
2.  Select settings items: Press the Select button 
 
to select the setting items 
show as Table 5.   
3.  Enter settings item: When the LCD display “LS1” or “LS2”, press the enter 
button 
  more than one second to enter the setting item and the settings 
string will flash. 
4.  Select setting value: Press the Select button 
 
to select the settings value. 
Select the value [001] or [000] to set the desired load segment ON or OFF. 
 
5.  Confirm settings: Press and hold the Enter button 
  for one
 second, ups