Caution:     
The EPO  must not be connected to any utility connected circuits. Reinforced 
insulation  to  the  utility  is  required.  The  EPO  Switch  must  have  a  minimum 
rating of 24Vdc and 20mA and be a dedicated latching-type switch not tied into 
any  other  circuit.  The  EPO  signal  must  remain  active  for  at  least  20ms  for 
proper operation 
 
 
EPO Connections 
Wire Function                      Terminal Wire Size Rating              Suggested Wire Size 
EPO                                          4-0.32mm
2
(12-22AWG)                  0.82mm
2
(18AWG) 
 
Note: Leave the green EPO connector installed in the EPO port of the UPS even 
if the EPO function is not need. Remove the small cable from EPO connector. 
   
 
 
 
 
                                   
 
EPO Connector 
 
 
5.3 Network Management Card (Optional) 
Network Management Card allows the UPS to communicate in a variety of 
networking environments and with different types of devices. The series UPS 
has one available communication slot for Webpower or other optional card to 
achieve remote management of the UPS through internet/ intranet. Please 
contact your local dealer for further information.