APC NetBotz 320 Rack Appliance NBRK0320E Manual De Usuario

Los códigos de productos
NBRK0320E
Descargar
Página de 210
Advanced View: Defining Thresholds
150
Using Your Appliance
c. When you have finished creating your Advanced Threshold, click OK to save the schedule and 
return to the Thresholds task.
– Select an Alert Severity value for this threshold. Available Alert Severities are, in order of 
escalating severity: Information, Warning, Error, Critical, or Failure. By default, the Alert 
Severity generated by this threshold will be “Error.”
– Specify the Alert Profile that will be used to determine what alert notification actions will be 
taken in response to this threshold. By default, the Default Alert Profile is used for all thresholds. 
However, if you have created additional Alert Profiles you can specify that a threshold use an 
Alert Profile other than Default.
– Select Cameras to Trigger in response to the alert. If desired, alert notifications generated in 
response to this threshold can include image captures from any Camera Pod 120s connected to 
your appliance. To include images from one or more connected Camera Pod 120s, check the 
check boxes that correspond to the desired pods. 
– Specify  a  User-specified URL and User-specified Description. You can use these fields to 
include additional user-specific information with any alert notifications that are generated using 
this threshold. 
8. Click OK to save this threshold.
Rate of Decrease Threshold 
rate of decrease threshold is defined by specifying a maximum acceptable decrease in value for the 
sensor and a period of time value. If the value reported by the sensor falls by more than the specified 
maximum acceptable decrease in less than the specified period of time an alert condition is reported. To 
define a rate of decrease threshold:
1. Start the Camera Pods, Sensor Pods, or Device Crawlers task by double-clicking on the appropriate 
icon.
2. Click Sensors... to open the Sensor Configuration window.
3. Select from the Sensors selection list the sensor for which you will define a threshold. A list of 
thresholds that have been previously defined for the selected sensor, if any, appears in the 
Thresholds selection list.
4. Click Add... to open the Select Threshold window. Select Rate of Decrease Threshold and then 
click OK to close the Select Threshold window.
5. Type in the Threshold Name field a name for this threshold.
6. Specify Basic threshold settings. From the Basic tab in the Thresholds pane:
a. Type in the Maximum Decrease field (or use the arrows in the field to specify) the highest 
acceptable change value for the selected sensor. If the value reported by the sensor decreases by 
more than the Maximum Decrease value in a period of time that is equal to or less than the 
number of seconds specified in the Time Period field, an alert condition results.
b. Type in the Time Period field (or use the arrows in the field to specify) the number of seconds 
that defines the unacceptable change period. If the value reported by the sensor decreases by 
Note
The Alert Profile drop box will appear in the Advanced tab only if additional 
Alert Profiles have been created. For more information see “Creating an Alert 
Profile” on page 63.