Bender RCMA420-D-2 B74043002 Hoja De Datos

Los códigos de productos
B74043002
Descargar
Página de 40
Function
11
ice.
3.2.6
Set the number of reload cycles
If faults occur only temporarily, but recurrently, in the system being moni-
tored, with the fault memory M deactivated, the alarm relays would switch 
synchronously to the error status.
RL in the out menu can be used to limit the number of these changeover proc-
esses. As soon as the preset number of switching cycles is exceeded, the fault 
memory will come on and an activated alarm remains stored.
3.2.7
Assigning alarm categories to alarm relays K1/K2
The alarm categories device error, residual current I
Δn1
, residual current I
Δn2
 or 
alarm by device test can be assigned to the alarm relays via the "out" menu.
3.2.8
Time delays 
t,  t
on 
 and 
t
off
The times tt
on
 and t
off, 
described below, delay the output of alarms via LEDs 
and relays.
3.2.9
Starting delay t
After connection to the supply voltage, the alarm indication is delayed by the 
preset time t (0...10 s).
3.2.10 Response delay 
t
on1/2
If the residual current increases above or falls below the response value the re-
sponse time t
an
 expires. After the expiry of the response time an alarm is sig-
nalled. A set response delay t
on1/2
 (0...10 s) adds up to the device-related 
operating time t
ae
 and delays alarm signalling (total delay time t
an
 = t
ae
 + t
on
).
If the residual current fault changes from a value above the response value to 
a value below the response value, an alarm will not be signalled.
3.2.11 Delay on release 
t
off
When no alarm exists after deactivating the fault memory, the alarm LEDs go 
out and the alarm relays switch back to their initial position. After activating 
the delay on release (0...99 s), the alarm state is continuously maintained for 
the selected period.