Bender RCMA420-D-2 B74043002 Hoja De Datos
Los códigos de productos
B74043002
9
3. Function
3.1
Device features
AC/DC sensitive residual current monitor Type B according to IEC
62020 and IEC 60755
62020 and IEC 60755
Two separately adjustable response ranges (prewarning, alarm)
Adjustable switching hysteresis
r.m.s. value measurement
Starting delay, response delay and delay on release
Measured value display via multi-functional LC display
Alarm indication via LEDs (AL1, AL2) and changeover contacts (K1, K2)
N/C operation or N/O operation selectable
Password protection against unauthorized parameter changing
Fault memory function can be switched off
CT connection monitoring
3.2
Function
Once the supply voltage U
s
is applied, the starting delay is activated. Meas-
ured values changing during this time do not influence the switching state of
the alarm relays. Residual current measurement takes place via an external
measuring current transformer of the W20AB…W60AB series. The currently
measured value is shown on the LC display. In this way any changes, for exam-
ple when circuits are connected to the system, can be recognized easily. If the
measured value exceeds one or both response values, the response delays
t
the alarm relays. Residual current measurement takes place via an external
measuring current transformer of the W20AB…W60AB series. The currently
measured value is shown on the LC display. In this way any changes, for exam-
ple when circuits are connected to the system, can be recognized easily. If the
measured value exceeds one or both response values, the response delays
t
on1/2
start running. Once the response delay t
on1/2
has elapsed, the K1/K2
alarm relays switch and the alarm LEDs AL1/AL2 light up. If the residual cur-
rent falls below the release value (response value minus hysteresis), the delay
on release t
rent falls below the release value (response value minus hysteresis), the delay
on release t
off
begins. Once the release delay t
off
has elapsed, the alarm relays
return to their original state and the alarm LEDs AL1/AL2 go out. If the fault
memory is activated, the alarm relays remain in the alarm state and the LEDs
light until the reset button is pressed or until the supply voltage is interrupted.
memory is activated, the alarm relays remain in the alarm state and the LEDs
light until the reset button is pressed or until the supply voltage is interrupted.