3/16                              CC1B-Hints-en 
Preliminary
                                 04.02.2003                                        HVAC Products 
2. Hints 
 
2.2 How to configure your RWF40 
 
 
Shown at the right is the basic display. 
 
 The current configuration of your specific  
controller will determine which levels you will be allowed  
to access. 
 
C112 must be xxx0 to access the configuration level. 
 
 
 
 
The C112 locking code can only be adjusted by the manufacturer. 
 
 
To reach the configuration level, you start from  
the basic display, (shown above), skip past the user  
level, and go first, to the parameter level, and  
then, finally, to the configuration level. 
 
Press  
 and hold for 3 seconds, and then release it. 
 
 
You are now at the parameter level. 
 
 
 
From the parameter level you may now advance  
to the configuration level,  
by pressing  
 again, holding, for 3 seconds,  
and then releasing it.  
 
The actual value display, (
9030
shows the current configuration value. 
 
The setpoint display, (
C111
shows the configuration item you are adjusting.  
 
 
 Configuration level items summary : 
 
C111 
Analog input 1
 
sensors (14 types), standard signal
 
 
Analog input 2
 
none, external SP, analog SP Shift
 
 
Analog input 3 
none, outdoor sensors … 
 
D2 function 
none, SP chg/over, SP binary shift 
 
C112
 
Limit comparator 
none, input 1,2,3 … 
 
Controller type 
3-position, modulating 0-20mA, … 
 
Setpoint SP1 
via buttons, with outside sensor 
 
Locking 
none, configuration, parameters, buttons 
 
C113
 Unit 
address 
Unit address 
0-9 
0-9 
 
Decimal - Units 
º C or º F and  decimals 
 
Signal out-of-range 
limit comparator OFF/ON 
 
SCL SC
ale 
L
ow Analog input 1 
SCH SC
ale 
H
igh Analog input 1 
 
SCL2 SC
ale 
L
ow Analog input 
2
 
SCH SC
ale 
H
igh Analog input 
 
SPL S
et 
P
oint, 
L
ower 
SPH S
et 
P
oint, 
H
igher 
 
OFF1 
Actual value correction, 
OFF
set, Analog input 
1
 
OFF2 
Actual value correction, 
OFF
set, Analog input 
2
 
OFF2 
Actual value correction, 
OFF
set, Analog input 
 
Df1 D
igital 
f
ilter time constant for Analog input 
1
 
Example    Re-configure (adjust) the value for C111 
 
 If no keys are pressed for 30 seconds, at anytime, the controller will 
automatically return to the basic display. 
 
 
The current value of C111, (
9030
)  
is shown in the actual value display. 
 
The current configuration item  (
C111
)  
is shown in the setpoint display. 
 
The display is steady, (not flashing) and by default,  
the 4
th
, (rightmost) digit is the one you may now  
adjust. 
 
 
You can select the digit you want to adjust,  
by pressing 
 once and releasing it. 
 
The 3
rd
 digit is now flashing, 
indicating that it is now, the adjustable digit. 
 
(Each time you press and release 
 you cycle, 
 thru each digit, right-to-left and back again) 
 
 
 
 
 
To change the value of the flashing digit,  
press 
 and release it.  
 
Each time you press 
 
and release, you cycle  
up thru the allowable values,  and back again. 
 
 
 
 
 
 
Once you have the desired value displayed  
and flashing, 
 you may accept it by pressing  
  once  
and releasing it.  
 
All four upper digits will flash once. 
 
The controller displays the new configuration  
values, in 4 steady digits. 
 
 
 
 
Your options at this point are: 
 
Press 
 
and release
,
 to immediately return to the basic display. 
or  
press 
 and release it, to advance to C112, 
press 
 
again and release it, to advance to C113, 
press 
 
and release it, to advance to SCL,  
 
 
… after the last configuration item Df1, 
 
press 
 
and release it, to advance to AL, (the 1
st
 parameter), 
 
 
… after the last parameter item P, 
 
press 
 
and release it, to advance to SP1, (the 1
st
 user item), 
 
 
… after the last user item it cycles back to the 1
st
 user item. 
 
Or simply wait 30 seconds and the controller will automatically  
return to the basic display.