Siemens RWF40 Manual De Usuario

Descargar
Página de 15
4/16                              CC1B-Hints-en 
Preliminary
                                 04.02.2003                                        HVAC Products 
2. Hints 
 
2.3 How to adjust parameters
 
 
 RWF40 user manual Section 6.3
 
 
 
Shown at the right is the basic display. 
 
 
 
The current configuration of your specific 
controller will determine which levels you will be  
allowed to access. 
 
C112 must be xxx1 or xxx0 to access the parameter  
level. 
 
 
The C112 locking code can only be adjusted by the manufacturer. 
 
 
From the basic display, you may skip the user level, to reach the 
parameter level. 
 
Press  
 and hold, for 3 seconds, and release. 
 
The actual value display, (
0
shows the current parameter value. 
 
The setpoint display, (
AL
shows the parameter item you are adjusting.  
 
 
 
 
Parameter level items summary:
 
 
AL A
larm 
L
imit value for comparator
 
HYSt 
Switching differential, 
Hyst
eresis for limit comparator
 
Pb.1 P
roportional 
b
and 
dt d
erivative
 t
ime
 
rt 
Integ
r
al action
 t
ime
 
db 
* 
d
ead 
b
and, contact spacing 
 
tt 
* Ac
t
uator running
 t
ime
 
HYS1 
Switch-on threshold, 
Hyst
eresis 
1
, 2-stage burner 
HYS2 
Switch-off threshold, 
Hyst
eresis 
2
, 2-stage burner 
HYS3 
Switch-off threshold, 
Hyst
eresis 
3
, upper 
Response threshold 
H H
eating curve slope 
P P
arallel displacement
 
 
 
* Items are only displayed when controller  
 
is configured for a 3-position output. 
 
Example    Adjust the value for parameter AL. 
 
 
 
 If no keys are pressed for 30 seconds, at anytime, the controller will 
automatically return to the basic display. 
 
 
The current value of AL, (
0
)  
is shown in the actual value display. 
 
The current parameter item (
AL
)  
is shown in the setpoint display. 
 
The display is steady, (nothing is flashing) 
and the value for AL can now be adjusted. 
 
 
 
 
 
 
You can  decrease 
You can increase 
the value  by 
the value by 
pressing  
 
pressing   
 
and releasing it. 
and releasing it. 
 
 
 
 
 
 
You can  accept 
Or, you can 
the change by 
advance to the 
waiting 2  seconds. 
Next parameter 
 
by pressing  
 
 once and 
The red LED’s will 
releasing it. 
blink once, and 
become the new 
HYSt can be 
value. adjusted 
the 
 
same way you 
 
just did AL. 
 
 
 
 
Your options at this point are: 
 
Press 
 
and release
,
 to immediately return to the basic display. 
 
Press 
 
and release it, to advance down to Pb.1,  
(the next parameter). 
 
… after the last parameter item P, press 
 
and release it,  
to advance down to SP1, (the 1
st
 user item). 
 
… after the last user item, the menu cycles back to the 1
st
 user item. 
 
Or simply wait 30 seconds and the controller will automatically return to 