Bacharach Ammonia Gas Monitor Single-Zone Manual De Propietario

Descargar
Página de 40
Single Zone Gas Monitor 
18 
P/N: 3015-4256 Rev 13 
3.2.  General Operation 
Once the SZ monitor has been installed, set up, and powered ON, the 
monitor will make measurements in the area being sampled for desired 
gas without further operator intervention. The results of those 
measurements are shown on the front panel display. 
 
In the example shown above, MEASURE  indicates that the SZ  unit  is actively monitoring  for  refrigerant 
gas, and that currently 45 ppm of R-134A (refrigerant gas) is being detected. This display also indicates 
that a peak measurement of 485 ppm has been made. 
An operator can reset the peak value to zero by pressing the ENTER button. 
A log of up to 200 previous measurements can be viewed using the PPM LOG function (page 22). 
If the detected gas level exceeds the preset Leak, Spill, or Evacuate alarm point, then the monitor 
responds by turning ON the front panel ALARM (red) light and energizing the corresponding alarm relay. 
If the internal audible alarm is turned ON, it too will activate (AUDALRM  page  22). Optional external 
alarm devices can be connected to the alarm relays to alert personnel that a Leak, Spill, or Evacuate 
alarm condition has occurred (page  14). Pressing the front panel SILENCE  button will acknowledge an 
alarm and turn OFF all alarm indicators with the exception of the front panel ALARM  light. The alarm 
circuit will reactivate, however, if the alarm condition is not cleared within the time period set by the 
SILENCE function (page 22). The ALARM light will turn OFF after the detected gas level goes below the 
lowest alarm point and after the SILENCE button is pressed. 
If a system fault occurs (see Fault Code list on page  23), the monitor responds by turning ON the front 
panel SYSTEM FAULT (yellow) light and energizing the fault relay. If the internal audible alarm is turned 
ON, it too will activate (AUDALRM page 22). An optional external alarm device can be connected to the 
fault relay to alert personnel that a system fault has occurred  (page  14). Pressing the front panel 
SILENCE  button will acknowledge the fault and turn OFF all alarm indicators with the exception of the 
front panel SYSTEM FAULT  light. The alarm circuit will reactivate, however, if the fault condition is not 
cleared within the time period set by the SILENCE function (page 22). The SYSTEM FAULT light will turn 
OFF only after the cause of the fault has been eliminated. 
A log of the  alarm and  fault events can be viewed using the monitor’s ALARMS and  FAULTS function 
(page 22). 
MEASURE  00485 pk       
   45ppm R134A