Single Zone Gas Monitor 
P/N: 3015-4256 Rev 13 
29 
4.5.  Fuses 
The  SZ monitor  is protected from  electrical damage by two, 1 A, 250 V, type “F” fuses (page  11)
Carefully remove the fuses from their fuse clips and visually inspect each fuse for damage. Replace the 
fuses as required (P/N 0004-2620). 
4.6.  Sample Pump 
The Sample Pump (page  11) draws the gas sample into the monitor, through the IR detector, and 
discharges the sample out the monitor’s exhaust port. When replacing the pump, remove its inlet and 
outlet tubing, disconnect the AC power wires from the pump itself, and remove pump from monitor. Install 
a new sample pump (P/N 3015-5176). 
4.7.  End-of-Line Water Stop (Optional) 
The end-of-line water stops (P/N 3015-5512)  prevent contaminates  and  moisture from entering the 
monitor.  This filter should be checked regularly and replaced when signs of contamination are obvious. 
4.8.  Water Trap (Optional) 
The water trap removes moisture that enters tubing before allowing it to enter the internal components of 
the SZ unit.  The water trap should be emptied often as condensate accumulates.  The water trap filter 
should be periodically checked and replaced when there are obvious signs of contamination. 
4.9.  Clock Battery 
The Clock Battery (page  11) maintains  the correct date and time when AC power is not applied to the 
monitor. Replace this battery about every 5 years (P/N 0204-0020).