GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
10 
3  Operation 
The GDA-1600 offers 3 graphic screens for viewing monitored data and a Set-Up menu 
screen for operator interface to configuration menus.  They are shown below in Figure 
3.0.  The Bar Graphs screen allows viewing of all active channels simultaneously.  The 
Trend screen displays a 24 hour trend, one channel at a time.  The Combination screen 
displays a bar graph, large engineering units and a 30 minute trend, one channel at a time.  
Input channels may be displayed in sequence with the UP/DOWN keys.  The NEXT key 
switches between the 3 graphic data screens.  When power is applied to the GDA-1600, 
the graphic LCD returns to the last active screen from when power was removed. 
Setup  menus are entered by pressing EDIT  from any data screen, and scrolling to the 
desired menu using the UP/DOWN  keys.  Pressing EDIT  again enters the selected 
menu’s tree of variables.  This Setup mode may be exited manually by pressing NEXT, 
or automatically when no keys are pressed for 5 minutes.  Alarm relays and front panel 
alarm LED indicators remain active during the Setup mode.  An AUTHORIZE menu 
offers a password feature to prevent tampering with GDA-1600 parameters. 
 
 
Figure 3.0 – Setup Menus 
3.1  Setup Menu Configuration 
Variables inside system and channel menu trees allow optimum GDA-1600 configuration 
for a wide range of demanding multi-point monitoring applications.  Access to menus are 
accomplished  via the Setup  mode by pressing EDIT  and activating the Setup  screen 
shown in Figure 3.0.  Menu trees are provided for each of the 16 channels and another for 
system variables.  Select the desired menu by scrolling with UP/DOWN and EDIT to 
enter the menus.