Bacharach GDA-1600 Manual De Propietario

Descargar
Página de 54
GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
2.2  Specifications 
Specification 
Description 
Input Power 
Standard GDA-1600 power requirements are 10-30VDC @ 3 watts applied to 
terminals 9 and 11 of TB2 on the standard I/O PCB (see section 4.0 on page 27). 
Optional features increase power consumption as described below: 
  Discrete Relay PCB option (5700-0012) - add 2 watts per PCB (assumes all 8 
relays are energized). 
  Analog Input PCB option (5700-0004) - add 1/2 watt. 
  4-20mA Output PCB option (5700-0005) - add 1 watt. 
  Catalytic Bead Sensor Input option (5700-0011) - add 12 watts max (assumes 
maximum sensor power consumption). 
  TB2 terminals 10 & 12 of the standard I/O PCB provide a maximum of 500mA 
fused output power for powering of auxiliary external devices such as relays, 
lamps or transmitters.  Power consumed from these terminals should be 
considered when calculating system power consumption. 
Power Supply 
150 Watt AC – 24VDC Power Supply (5700-0007) 
  110-120 VAC* @3.2A max 
  220-240VAC* @ 1.6A max 
* A slide switch on the front of the power supply selects AC input range. 
Relays 
 
Common relays are standard and menus provide voting logic for 
ALARM 1, ALARM 2, FAULT,  and HORN.  Discrete relays are 
optional.  All relays are rated at 5 Amp for 28 VDC and 250 VAC 
RESISTIVE loads. 
 
IMPORTANT:   Appropriate diode (DC load) or MOV (AC load) snubber devices must 
be installed with inductive loads to prevent RFI noise spikes.  Relay 
wiring should be kept separate from low-level signal wiring.
 
Temperature 
-25 to 50 degrees C (Ambient) 
Humidity 
0 to 90% R. H. Non-condensing 
Altitude 
Recommended up to 2000 meters  
Housings 
  General purpose panel mount weighing 7 lbs and including hardware for 19” 
rack mounting (Figure 7.1 on page 43).
  NEMA 4X wall mount in fiberglass enclosure weighing 17 lbs (see Figure 7.2 on 
page 44).
* Includes non-intrusive magnetic keypad (see below) 
Keypad 
Non-intrusive; Magnetic 
The operator interface includes five front panel touch keys.  A magnetic keypad 
offers these five keys with adjacent magnetic keys as a standard feature.  It is useful 
in applications where it may be inconvenient to open the enclosure’s door to access 
the touch keypad. 
Approvals 
CSA C22.2 No 1010.1 and ISA S82.02 
CSA C22.2 No 152 for combustibles 
UL 1604 / C22.2 No 213 (Div 2 Groups A,B,C,D) 
EN55011 & EN61000 (CE Mark) 
CSA File # = 219995 and may be seen at:  CSA-International.org.