Bacharach GDA-1600 Manual De Propietario

Descargar
Página de 54
Instruction 5700-9001 
 
GDA-1600 16-Channel Controller 
13 
3.2.2  Alarm 1 / Alarm 2 / Horn Relay Setup Menu 
Alarms 1 and 2 are identical except A1 may not be acknowledged and front panel LED 
indicators are yellow while A2s are red.  Since their configuration menus are the same 
only one is shown in Figure 3.2 for clarity. 
 
Figure 3.2 – Alarm / Horn Relay Setup Menu 
 
Entries 
Description 
Setpoint 
Value where the alarm trips.  It is entered in engineering units.  For example, if a 
channel monitors 0-50 ppm H
2
S and the alarm is to trip at 10 ppm, the correct entry is 
10.00. 
Latching 
Determines either manual or automatic alarm reset operation.  YES requires a manual 
Alarm Reset to unlatch the alarm even though an alarm condition no longer exists.  YES 
also causes this alarm group’s common relay, front panel LED, and optional discrete 
relay to latch.  NO allows all outputs for this alarm to automatically reset as soon as the 
alarm condition clears. 
Trip On 
TRIP ON is set to HIGH for increasing alarms or LOW for decreasing alarms to determine 
if the alarm activates upon exceeding or falling below the setpoint. 
On/Off 
Delay 
Allow  ON  and  OFF  time delays affecting how long the setpoint must be surpassed 
before an alarm event transition occurs.  ON delays are limited to 10 seconds while OFF 
delays may be as long as 120 minutes.   Delays are useful in many applications to 
prevent nuisance alarms and unwanted cycling into and out of alarm conditions. 
Horn On 
Used to link this alarm to the common horn relay.  NO  causes the alarm to have no 
effect upon the horn relay.  Entering YES causes this alarm to turn the horn relay on 
steady, or, to pulse it depending upon horn configuration in they system menu (see 
section 3.3.1). 
 
Discrete LED indicators on the front panel indicate the status of each alarm and relay.  
Any  new  alarm event causes the associated LED to flash until Alarm Reset  occurs 
causing an acknowledged, steady on condition.  Operators should recognize new alarms 
by a flashing LED.  Alarm Reset also acknowledges, or deactivates, the horn relay until 
another new alarm occurs. 
All relays are rated at 5 Amp for 28 VDC and 250 VAC RESISTIVE loads.   
 
 
IMPORTANT:  Appropriate diode (DC loads) or MOV (AC loads) 
snubber devices must be installed with inductive loads to prevent RFI noise 
spikes.  Relay wiring should be kept separate from low level signal wiring.