GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
14 
3.2.3  Alarm 3/Fault Alarm Menu 
The discrete channel alarms identified as Alarm 3/Fault may be configured either as a 3
rd
 
level alarm or  as a Fault alarm indicating the input is out of range in the negative 
direction.  When used as a level alarm, features such as on / off delays, latching, and trip 
direction are also available.  It is important to understand that though discrete channel 
alarms (LEDs  and  optional discrete relays) may be set as Alarm 3 level alarms, the 
common relay for this group is always a Fault alarm.  The fault out of range threshold for 
the channel is the most recent Fault trip point entered prior to changing the menu to 
Alarm 3.  The following example describes how to configure both the Fault out of range 
and Alarm 3 level trip points for a channel.   
 
Example:  If the common Fault relay must trip as the input falls below negative 10% of 
full scale, and the discrete alarms trip as the input exceeds a level, then the -10% Fault 
setpoint must be entered first.  Toggle the TYPE  menu entry to 
FAULT  and enter 
-10.00% into the setpoint entry.  Next, toggle the menu back to 
LEVEL and enter the 
desired Alarm 3 level setpoint.  The -10% Fault value is retained in memory even though 
it no longer appears on the menu. 
 
Figure 3.3 – Alarm / Fault Menus 
3.2.4  Data From Menu to Set Input Source 
Channels  may be independently configured to accept input data from the following 
sources (also see Figure 3.4): 
  An analog input PCB attached to the I
2
C bus. 
  A sensor input PCB attached to the I
2
C bus. 
  The Modbus RS-485 master port connected to Modbus slave devices. 
 
NOTE:  Each  Modbus  menu selection also requests the RTU # and the Alias 
register # location of the data to be retrieved from the RTU.  Alias register 
numbers define the location of the variable representing the input value and 
must be obtained from the manufacturer of the Modbus RTU device. 
 
EDIT toggles the Data From: entry between Analog, Analog with Local Cal or Sensor 
Direct, and Modbus RTU (signed, unsigned & floating point).