GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
16 
 
 
Figure 3.4 – Input Data Sources 
 
3.2.4.1  Min / Max Raw Counts Menus 
 
Entries 
Description 
Min Raw 
The Minimum and Maximum Raw count entries, included in Input Data from menus, 
define the range of input counts that provide Measurement Range read-out values 
described in section 3.2.6.2 (on page 19).  This menu entry is determined by the A/D 
converter resolution of the channel’s input.  For example, if the input is a 10 bit 
Modbus® device with zero at 200 counts and 100% at 1000 counts, then this menu’s 
MIN should be set at 200 and MAX at 1000.  If communicating with the GDA-1600’s 
optional 12-bit Analog Input PCB, the MIN should be 800 and the MAX should be 
4000. 
If the input device’s resolution is unknown, the live counts variable on the bottom of 
the screen displays the actual raw A/D counts currently being read by this channel.  
This reading may be used to test the input device for what A/D counts are provided 
for zero and 100% if these values are unknown.  Forcing the input device to read 
zero should provide the A/D counts value needed to make this channel’s display also 
read zero.  Likewise, forcing the input device to read 100% should provide the A/D 
counts value needed to make the GDA-1600 channel’s display also read 100%. 
If Modbus 32 BIT is selected, a Byte Order entry appears at the bottom of the menu.  
This determines WORD and BYTE alignment of data at the remote Modbus 
transmitter when sending its 4 byte IEEE Floating Point values.  With the pointer on 
this entry, the EDIT key toggles between the 4 possible modes.  Min / Max Raw 
values are not used in this mode. 
Max Raw 
 
NOTE:  Each Data From: item has a matching default Min/Max counts value of 20% to 
100% with ± 5% over/under range applied.  If the default value is incorrect for 
the input device it should be edited.