GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
24 
Entries 
Description 
Piezo Alarm 
Turning Piezo Alarm ON causes the audible piezo to duplicate the action of the horn 
relay.  This feature may be used to provide a low decibel indication of the status of the 
system’s horn. 
Alarm 1 
Alarm 1 & Alarm 2 menus control how this alarm level from each channel will affect 
the common horn relay.  Choices are OFF,  ON  or  BEEP  (one Hz. Pulsating).  As an 
example, A2 conditions might pulse  the horn (BEEP) and A1 conditions to cause a 
steady horn (ON).  Any other combination of these 3 choices is possible for A1 and A2 
levels affecting the horn relay.  This feature is very useful since it allows the horn relay 
to serve as another level A1, level A2, or both; for channels 1-16, 1-8 or 9-16.  
Individual channel alarms may also be configured to not affect the Horn relay on a 
channel by channel basis (see section 3.2.2 on page 13). 
Alarm 2 
Failsafe 
Failsafe  &  Horn Group menu entries are identical to the descriptions for menus 
Common Relay 1 & Common Relay 2 in section 3.3.1. 
Horn Group 
Acknowledge  Turning Acknowledge OFF allows the common Horn relay to drive devices other than 
horns or sirens such as a light or a fan.  
Display Alm 
Display Alm YES forces the LCD to display the Bar Graphs screen upon any new alarm.  
This feature is offered to satisfy applications requiring channels in alarm to be 
displayed automatically (all channels are displayed on the Bar Graphs screen). 
3.3.4  Comm Port Menus 
Entries 
Description 
Slave ID 
The system Comm Port menu (see Figure 3.10) allows for setting of the RTU Slave ID 
address, Slave Baud rate, Parity and UART Timer for the comm2 slave Modbus serial 
port (comm1 master  port ID settings are per channel as described in section 3.2.4).  
This slave port may be used to transfer GDA-1600 data to a host device such as a PC, 
PLC, DCS or even another GDA-1600.  The slave port is addressable, allowing many 
GDA-1600 controllers to be connected to a single RS-485 cable.   
Slave Baud 
Parity 
UART Timer 
The UART Timer setting is disabled with 00 seconds entered.  Entering a value causes 
the comm2 slave  Modbus serial port to reinitialize if no Modbus  query is processed 
within this time period.  This ensures against serial port lockup.  Section 6 of this 
manual provides important information describing how to interface to the GDA-1600’s 
Modbus slave port. 
Mastr TO 
The Mastr TO (master time out) and Mastr PR (master poll rate) menu items affect the 
GDA-1600’s  master  Modbus port.  Time out  sets the length of time in milliseconds 
before a communications error.  Three consecutive timeout errors must occur before a 
communication error is indicated.  This item is useful for optimizing throughput to the 
GDA-1600 from other slave RTUs.  Poll Rate  sets frequency of data requests to the 
RTUs in milliseconds.  This is useful when an RTU is limited in how fast it may respond 
to consecutive data requests. 
Mastr PR 
Echo ACK 
The  Echo ACK (echo  acknowledge) menu allows alarm reset / alarm acknowledge 
functions be sent from the Modbus master port to connected Modbus  slave devices 
having Modbus coil 2001 assigned as the reset / acknowledge coil.  This menu may be 
set to OFFLCL (local) or MB/LCL (Modbus/local).  Off disables the feature and 2001 
coils of slave devices are unaffected.  LCL only writes to the 2001 coils of connected 
RTUs when the local Reset pushbutton is pressed.  MB/LCL  writes these coils if  this 
GDA-1600’s 2001 coil has been reset via Mobus AND when the local pushbutton is