Bacharach GDA-1600 Manual De Propietario

Descargar
Página de 54
Instruction 5700-9001 
 
GDA-1600 16-Channel Controller 
25 
Entries 
Description 
pressed.  The MB/LCL option is useful if GDA-1600s are being cascaded from and HMI 
or other Modbus master.  A short time delay between reset of remote RTUs and the 
primary GDA-1600 may occur since remote resets are processed first. 
 
IMPORTANT!  ALL MODBUS 2001 COILS ARE WRITTEN BY THIS 
FEATURE.  DO NOT CONNECT DEVICES WITH 2001 COILS 
CONTROLLING OTHER CRITICAL EVENTS! 
     
3.3.5  Eight / Sixteen Channel Modes 
The system menu allows for setting of the GDA-1600 controller to accept either 8 or 16 
channels.  If 8 channels are selected by this menu they are channels 1-8 and 9-16 become 
disabled.  One way GDA-1600  cost is kept low is Input / Output option PCBs  are 
arranged into groups of 8 channels.  Therefore, users with less than 9 channels require 
only 1 PCB and do not pay for I/O hardware for 16 channels.  If more than 8 channels are 
needed a second I/O option PCB may be required. 
 
Figure 3.15 – Channel Configuration 
3.3.6  Sensor Information 
Sensor Info  is available when  at least one channel has  Sensor Life activated in the 
Marker  menu (see section 3.2.4.2).  The  Sensor Info  screen displays each channel’s 
sensor status as illustrated in Figure 3.16.  Channels with Sensor Life disabled indicate 
Option Disabled above the corresponding empty bar-graph.  If Sensor Life is enabled, 
the channel will have its Measurement Name above the bar, or, an empty bar with a 
Cal 
Required  label.  Cal Required indicates  no Calibration Marker value  has been 
received by the GDA-1600. 
 
Figure 3.16 – Sensor Information