15. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
15.5.2 List of details
No. Symbol
Name and function
Initial
value
value
Unit
Setting
range
PA01 *REG Regenerative
option
Used to select the regenerative option.
Select the regenerative option.
00: No used
01: MR-RB139
02: MR-RB137(3 pcs.)
11: MR-RB136-4
12: MR-RB138-4(3 pcs.)
"01" and "02" are the set values for the MR-J3-CR55K only, and "11"
and "12" are those for the MR-J3-CR55K4 only.
Incorrect setting will result in parameter alarm (A.37).
00: No used
01: MR-RB139
02: MR-RB137(3 pcs.)
11: MR-RB136-4
12: MR-RB138-4(3 pcs.)
"01" and "02" are the set values for the MR-J3-CR55K only, and "11"
and "12" are those for the MR-J3-CR55K4 only.
Incorrect setting will result in parameter alarm (A.37).
0
0
Only for MR-J3-CR55K
Only for MR-J3-CR55K4
0000h
Refer
to
Name
and
function
column.
and
function
column.
PA02 *MCC Magnetic contactor drive output selection
Used to select the output of the magnetic contactor drive power supply.
Used to select the output of the magnetic contactor drive power
supply.
0: No used
1: Used
supply.
0: No used
1: Used
0
0
0
0001h
Refer
to
Name
and
function
column.
and
function
column.
PA03 For manufacturer setting
0001h
PA04
Do not change this value by any means.
0
PA05
100
PA06
0
PA07
100
PA08 *DMD Status display selection
Used to select the status display shown at power-on.
Status display of converter unit display section at power-on.
0: Status
1: Bus voltage
2: Effective load ratio
3: Peak load ratio
4: Regenerative load ratio
0: Status
1: Bus voltage
2: Effective load ratio
3: Peak load ratio
4: Regenerative load ratio
0 0
0
0000h
Refer
to
Name
and
function
column.
and
function
column.
PA09 *BPS Alarm history clear
Used to clear the alarm history.
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid, the alarm history is cleared
at next power-on.
After the alarm history is cleared, the setting is automatically made
invalid (reset to 0).
0: Invalid
1: Valid
When alarm history clear is made valid, the alarm history is cleared
at next power-on.
After the alarm history is cleared, the setting is automatically made
invalid (reset to 0).
0 0
0
0000h
Refer
to
Name
and
function
column.
and
function
column.
PA10 For manufacturer setting
0
PA11
Do not change this value by any means.
0000h