15. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW) 
 
15.9.10 FR-BU2-(H) brake unit 
POINT 
 
Use a 200V class brake unit and a resistor unit with a 200V class converter unit, 
and a 400V class brake unit and a resistor unit with a 400V class converter unit. 
Combination of different voltage class units cannot be used. 
Install a brake unit and a resistor unit on a flat surface vertically. When the unit is 
installed horizontally or diagonally, the heat dissipation effect diminishes. 
Temperature of the resistor unit case rises to higher than 100 . Keep cables 
and flammable materials away from the case. 
Ambient temperature condition of the brake unit is between  10  (14 ) to 50  
(122 ). Note that the condition is different from the ambient temperature 
condition of the converter unit (between 0  (32 ) to 55  (131 )). 
Configure the circuit to shut down the power-supply with the alarm output of the 
brake unit and the resistor unit under abnormal condition. 
Use the brake unit with a combination indicated in (1) in this section. 
For executing a continuous regenerative operation, use FR-RC-(H) power 
regenerative converter or FR-CV-(H) power regenerative common converter. 
When using the brake unit, set the parameters as shown below. 
 
   Setting 
value 
 
 
Parameter No.PA01 of the MR-J3-CR55K(4) converter unit 
00 (Initial value) 
 
 
Parameter No.PA02 of the drive unit 
00 (Initial value) 
 
 
 
 
 
 
Connect the brake unit to the bus of the converter unit (L  and L  of TE2-1) for use. As compared to the MR-
RB regenerative option, the brake unit can return larger power. Use the brake unit when the regenerative option 
cannot provide sufficient regenerative capability. 
When using the brake unit, make sure to refer to the FR-BU2-(H) Brake Unit Instruction Manual. 
 
(1) Selection 
Use a combination of converter unit, brake unit and resistor unit listed below. 
 
Brake unit 
Resistor unit 
Number of 
connected 
units 
Permissible 
continuous 
power [kW] 
Total 
resistance 
[ ] 
Applicable converter 
unit 
200V 
class 
FR-BU2-55K FR-BR-55K 
(parallel) 7.82 
1 MR-J3-CR55K 
 MT-BR5-55K 
(parallel) 
11.0 
MR-J3-CR55K 
400V 
class 
FR-BU2-H55K FR-BR-H55K 
(parallel)  7.82 
4  MR-J3-CR55K4 
FR-BU2-H75K MT-BR5-H75K  2 
(parallel)  15.0 
3.25 MR-J3-CR55K4