VENT INSTALLATION 
HORIZONTAL TERMINATION CONFIGURATIONS
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue 
gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the vari-
ous dimensions allowable. See page 20. 
Minimum clearance between vent pipes and combustible materials is 3" on top and 1" from bottom and sides unless 
otherwise noted.
When vent termination exits through foundations less than 20" below siding outcrop, the vent pipe must flush up with 
the siding.
It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of he Transi-
tion Elbow) to the face of the outer wall. 
When  installing  the  appliance  as  a  rear  vent  unit,  the  90°  or  45°  transition  elbow 
attached directly to the rear of the unit is NOT INCLUDED in the following criteria and 
calculations, and unless specifically mentioned should be ignored when calculating 
venting layouts.
W
ARNING
Figure 25 - Maximum Three (3) 90° Elbows 
Per Installation
•   The maximum number of 90° elbows per side wall installation is three (3). See Figure 25. 
•   If a 90° elbow is fitted directly on top of the fireplace flange the maximum horizontal vent run before the termination or 
a vertical rise is 36” (914 mm). See Figure 26.
Figure 26 - Maximum Horizontal Run with No Rise
3 x 90°
Elbows
3 x 90°
Elbows
36"
Max.
36"
Max.