•   If  a  90°  elbow  is  used  in  the 
horizontal vent run, the horizon-
tal vent length is reduced by 36" 
(914 mm). See Figure 28. This 
does not apply if the 90° elbows 
are used to increase or redirect 
a vertical rise. See Figure 29.
Example: According to the vent 
graph,  Figure  27,  the  maxi-
mum horizontal vent length in a 
system  with  a  7.5'  vertical  rise 
is 20’ (6m) and if a 90° elbow is 
required in the horizontal vent it 
must be reduced to 17' (5.2 m). 
See page 22 “How to Use Vent 
Graph.”
In  Figures  28  and  29,
 Dimension 
A plus B must not be greater than 
17' (5.2m).
•   The maximum number of 45° 
elbows permitted per side wall 
installation  is  two  (2). These 
elbows can be installed in either the vertical or horizontal run. 
•   For each 45° elbow installed in the horizontal run, the length of the horizontal run 
MUST be reduced by 18" (45cm). This does not apply if the 45° elbows are installed 
on the vertical part of the vent system.
•   The maximum number of elbow degrees in a system is 270°. See Figure 30.
Figure 29 - Maximum Vent Run with Elbows
Example: 
Elbow 1   =   90°
 
Elbow 2   =   45°
 
Elbow 3   =   45°
 
Elbow 4   =   90°
Total Angular Variation  =   270°
Figure 30 - Maximum Elbow Usage 
VENT INSTALLATION 
A + B = 17' Maximum
90° Elbow = 3'
1 + 2 + 3 + 4 = 270°
1
2
3
4
1
2
3
4
Figure 28 - Horizontal Run Reduction 
90°
7'6"
A
B
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
2 4 6 8 10 1214 16 1820
eg: A
Figure 27 - Rear Wall 
Venting Graph
Horizontal Dimension From the 
Outside Face of the Wall to the 
Center of the Fireplace Vent 
Flange
HORIZONTAL TERMINATION CONFIGURATION (Continued)